Category: Public Works
Client: Municipal Authority in California

Condition Assessment and Repair Recommendation for a CA Sewage Treatment Plant.

Cross Sectional Elevation.jpg
Photo 5.JPG

Coating Failure

The visual inspection showed that the exterior of the structure was generally in good condition, but the roof dome had some minor cracking. The interior coating had several cracks, delamination, and minor spalls.

 
 
Photo+6.jpg
Photo 7.JPG

Testing for Metal Thickness

The upper skimmer arms had broken ties and exhibited heavy corrosion, especially on metal angles. The intermediate shaft also showed substantial corrosion at some locations.The sewage generates hydrogen sulfide. Hydrogen sulfide caused deterioration in concrete and corrosion of exposed metal parts such as skimmer.

Photo 8.JPG

Condition of Reinforcement

The testing consisted of coring, inspection of reinforcing steel nondestructive impact echo tests, Rebound hammer tests, coring, strength tests, chloride tests,& concrete petrography.

Photo 9.JPG

Repairs were designed to extend the service life structure by 25 years. The repairs consisted of epoxy injection, spall repair, applying low permeability overlay, and a 100% solid coating to resist hydrogen sulfide related deterioration.

Next
Next

Bakersfield Hall of Records